Product successfully added to your shopping cart
PT-IQ-2X1-24DC-UT
2800787
PHOENIX_CONTACT
1
Surge protection device
Trabtech (TT)
* Brand new product in its original packaging covered by the warranties and certifications provided by PHOENIX_CONTACT
Thank you for your interest in our products; we hope the delivery time indicated is to your convenience.
While the order is being processed you can select the type of shipment that best suits your needs: 24-hour air express, standard 48-72 hour land, etc.
Orderkey | 2800787 |
---|---|
Packing unit | 1 pc |
Catalog page | Page 110 (C-4-2017) |
GTIN | 4046356645218 |
Weight per Piece (excluding packing) | 106.200 g |
Custom tariff number | 85363010 |
Country of origin | DE (Germany) |
Ambient temperature (operation) | -40 °C ... 70 °C |
---|---|
Ambient temperature (storage/transport) | -40 °C ... 85 °C |
Altitude | ≤ 4000 m (amsl (above mean sea level)) |
Degree of protection | IP20 |
Housing material | PA 6.6 |
---|---|
Flammability rating according to UL 94 | V-0 |
Color | jet black RAL 9005 |
Mounting type | DIN rail: 35 mm |
Type | DIN rail module, two-section, divisible |
Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
---|
IEC test classification | C1 |
---|---|
C2 | |
C3 | |
D1 | |
Nominal voltage UN | 24 V DC |
Maximum continuous voltage UC | 30 V DC |
21 V AC | |
Rated current | 1000 mA (40 °C) |
Operating effective current ICat UC | ≤ 1 mA (per path) |
Residual current IPE | ≤ 1 mA (per path) |
Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
Total discharge current Itotal(8/20) µs | 20 kA |
Voltage protection level Up(line-earth) | ≤ 75 V (C1 - 1 kV/500 A) |
≤ 135 V (C2 - 10 kV / 5 kA) | |
≤ 55 V (C3 - 25 A) | |
≤ 60 V (C3 - 50 A) | |
Response time tA(line-earth) | ≤ 1 ns |
Input attenuation aE, asym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 1.1 MHz |
Capacity (line-earth) | typ. 2 nF |
Resistance in series | 1.2 Ω ±5 % |
Surge protection fault message | Optical, multi-stage |
Max. required back-up fuse | 1 A (FF) |
Impulse durability (line-earth) | C1 - 1 kV/500 A |
C2 - 10 kV/5 kA | |
C2 - 10 kA | |
C3 - 50 A | |
D1 - 2.5 kA | |
Pulse reset time (line-earth) | ≤ 350 ms |
Connection method | Screw connection |
---|---|
Screw thread | M3 |
Tightening torque | 0.5 Nm |
Stripping length | 8 mm |
Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
Conductor cross section solid | 0.2 mm² ... 4 mm² |
Conductor cross section AWG | 24 ... 12 |
Standards/specifications | IEC 61643-21 2000 + A1:2008, modified |
---|---|
EN 61643-21 2001 + A1:2009 | |
EN 61000-6-3 2007 + A1:2011 | |
EN 61000-6-2 2005 |
Title: | Size: | Type: |
---|---|---|
PDF CATALOG PHOENIX PROTECTION EN.pdf | 27 Mbytes | |
PHOENIX CONTACT-2800787-PT-IQ-2X1-24DC-UT | 141 Kbytes |
No customer reviews for the moment.
Rating: | |
Name: | |
Email: | |
Subject: | |
Text: | |
Do you recommend this product to buy? | |
Add review |
All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.