3RT1482-6AF36 SIEMENS Power contactor, AC-1 1050 A, 3-pole AC (50...60 Hz) / DC operation 100...127 V AC / 1.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details.

3RT1482-6AF36 SIEMENS Power contactor, AC-1 1050 A, 3-pole AC (50...60 Hz) / DC operation 100...127 V AC / 1..

3RT1482-6AF36

SIEMENS

Power contactor, AC-1 1050 A, 3-pole AC (50...60 Hz) / DC operation 100...127 V AC / 100...110 V DC Operating mechanism: electronic Auxiliary contacts 2 NO + 2 NC Busbar connections Auxiliary switch and coil connections in screw-type technology

Power contactor, AC-1 1050 A, 3 poles AC (50...60 Hz)/DC control 100...127 V AC/100...110 V DC Drive: electronic auxiliary contact blocks 2 NA + 2 NC bar connections auxiliary contact blocks and coil connections in screwable version

More details


CONTROL AND CONTACTORS > Contactors for switching motors

* Brand new product in its original packaging covered by the warranties and certifications provided by SIEMENS

Total price: $4,011.39
Unit price: $4,011.39

*This price is per unit and is the net value (not including taxes if applicable).

If our price is not the best, please ask us for a quote. Ask for a quotation

Best sellers

More info



Technical data

Power contactor, AC-1 1050 A, 3-pole AC (50...60 Hz) / DC operation 100...127 V AC / 100...110 V DC Operating mechanism: electronic Auxiliary contacts 2 NO + 2 NC Busbar connections Auxiliary switch and coil connections in screw-type technology
product brand nameSIRIUS
product designationContactor
product type designation3RT14
General technical data
product extension
● function module for communicationNo
● auxiliary switchYes
power loss [W] for rated value of the current
● at AC in hot operating state510 W
● at AC in hot operating state per pole170 W
● without load current share typical6 W
insulation voltage
● of main circuit with degree of pollution 3 rated value1 000 V
● of auxiliary circuit with degree of pollution 3 rated value600 V
surge voltage resistance
● of main circuit rated value8 kV
● of auxiliary circuit rated value6 kV
shock resistance with sine pulse
● at AC8g / 11 ms
● at DC8g / 11 ms
mechanical service life (switching cycles)
● of contactor typical1 000 000
Substance Prohibitance (Date)03/27/2020
Ambient conditions
installation altitude at height above sea level maximum2 000 m
ambient temperature
● during operation-25 ... +55 °C
● during storage-40 ... +80 °C
relative humidity minimum10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum95 %
Main circuit
number of poles for main current circuit3
number of NO contacts for main contacts3
number of NC contacts for main contacts0
type of voltage for main current circuitAC
operational current
● at AC-1
— up to 690 V at ambient temperature 40 °C rated value1 050 A
— up to 690 V at ambient temperature 55 °C rated value1 050 A
— up to 1000 V at ambient temperature 40 °C rated value1 050 A
— up to 1000 V at ambient temperature 55 °C rated value1 050 A
minimum cross-section in main circuit at maximum AC-1 rated value800 mm²
no-load switching frequency
● at AC600 1/h
● at DC600 1/h
operating frequency at AC-1 maximum600 1/h
Control circuit/ Control
type of voltage of the control supply voltageAC/DC
control supply voltage at AC
● at 50 Hz rated value100 ... 127 V
● at 60 Hz rated value100 ... 127 V
control supply voltage at DC
● rated value100 ... 110 V
operating range factor control supply voltage rated value of magnet coil at DC
● initial value0.85
● full-scale value1.1
operating range factor control supply voltage rated value of magnet coil at AC
● at 50 Hz0.85 ... 1.1
● at 60 Hz0.85 ... 1.1
design of the surge suppressorwith varistor
apparent pick-up power of magnet coil at AC
● at 50 Hz1 000 VA
● at 60 Hz1 000 VA
apparent holding power of magnet coil at AC
● at 50 Hz18 VA
● at 60 Hz18 VA
closing power of magnet coil at DC1 400 W
holding power of magnet coil at DC6 W
closing delay
● at AC80 ms
● at DC80 ms
opening delay
● at AC70 ms
● at DC70 ms
control version of the switch operating mechanismStandard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts2
● attachable4
● instantaneous contact2
number of NO contacts for auxiliary contacts2
● attachable4
● instantaneous contact2
operational current at AC-12 maximum16 A
operational current at AC-15
● at 230 V rated value3 A
● at 400 V rated value1.5 A
● at 500 V rated value1.4 A
operational current at DC-13
● at 48 V rated value2 A
● at 60 V rated value2 A
● at 110 V rated value1 A
● at 125 V rated value0.55 A
● at 220 V rated value0.27 A
● at 600 V rated value0.1 A
Short-circuit protection
product function short circuit protectionNo
design of the fuse link
● for short-circuit protection of the main circuit
— with type of assignment 2 requiredaR: 1100 A (1000 V, 42 kA)
● for short-circuit protection of the auxiliary switch requiredgG: 16 A (600 V, 1 kA)
Installation/ mounting/ dimensions
mounting position+/-30° rotation possible on vertical mounting surface; can be tilted forward and backward by +/- 30° on vertical mounting surface
fastening methodscrew fixing
● side-by-side mountingNo
height352 mm
width285 mm
depth250 mm
required spacing
● for grounded parts
— forwards125 mm
— at the side75 mm
net weight22.2 kg
Connections/ Terminals
type of electrical connection
● for main current circuitbusbar connection
● for auxiliary and control circuitscrew-type terminals
● at contactor for auxiliary contactsScrew-type terminals
● of magnet coilScrew-type terminals
width of connection bar40 mm
thickness of connection bar10 mm
diameter of holes17 mm
connectable conductor cross-section for auxiliary contacts
● solid or stranded1 ... 2.5 mm²
● finely stranded with core end processing1 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid2x (1 ... 2,5 mm²)
— solid or stranded2x (1 ... 2,5 mm²)
— finely stranded with core end processing2x (1 ... 2,5 mm²)
● at AWG cables for auxiliary contacts2x (16 ... 14)
Safety related data
product function
● mirror contact according to IEC 60947-4-1Yes
● positively driven operation according to IEC 60947-5-1No
protection class IP on the front according to IEC 60529IP00
Certificates/ approvals

Downloads and manuals

General Product ApprovalEMCDeclaration of Conformity

CCC

Confirmation

UL

EAC

RCM

EC/EU-Declaration of Conformity

Declaration of ConformityotherRailway

UK Declaration of Conformity

Confirmation

Miscellaneous

Special Test Certificate

Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
Industry Mall (Online ordering system)
Cax online generator
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
Characteristic: Tripping characteristics, I²t, Let-through current
Further characteristics (e.g. electrical endurance, switching frequency)
last modified:3/15/2022
Date
5/8/2022
Subject to change without notice
© Copyright Siemens 2022


Additional data

Product
Article Number (Market Facing Number)3RT1482-6AF36
Product DescriptionPower contactor, AC-1 1050 A, 3-pole AC (50...60 Hz) / DC operation 100...127 V AC / 100...110 V DC Operating mechanism: electronic Auxiliary contacts 2 NO + 2 NC Busbar connections Auxiliary switch and coil connections in screw-type technology
Product familySIRIUS 3RT.4 contactors for weak or non-inductive loads (AC-1), 3-pole up to 2 650 A
Product Lifecycle (PLM)PM300:Active Product
Price data
Region Specific PriceGroup / Headquarter Price Group41B / 41B
Surcharge for Raw MaterialsNone
Metal FactorNone
Delivery information
Export Control RegulationsAL : N / ECCN : EAR99
Standard lead time ex-works5 Day/Days
Net Weight (kg)20,100 Kg
Packaging Dimension320,00 x 400,00 x 300,00
Package size unit of measureMM
Quantity Unit1 Piece
Packaging Quantity1
Additional Product Information
EAN4047621054728
UPC195125051331
Commodity Code85364900
LKZ_FDB/ CatalogIDCC-IC10
Product Group2234
Group CodeR711
Country of originSouth Korea
Compliance with the substance restrictions according to RoHS directiveSince: 27.03.2020
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
WEEE (2012/19/EU) Take-Back ObligationYes
REACH Art. 33 Duty to inform according to the current list of candidates

Information obligation imposed by Article 33, REACH Regulation: This product includes one or several articles in which the following substance of the candidate list is contained in concentrations higher than 0,1% weight by weight (w/w):

Lead

Based on the information currently available, we assume that these substances do not pose any risk if the articles are used as intended (including disposal). Please also refer to product documentation.

Classifications
VersionClassification
eClass627-37-10-03
eClass7.127-37-10-03
eClass827-37-10-03
eClass927-37-10-03
eClass9.127-37-10-03
ETIM5EC000066
ETIM6EC000066
ETIM7EC000066
ETIM8EC000066
IDEA44755
UNSPSC1539-12-15-29

Datasheet - PDF

Reviews (0)

No customer reviews for the moment.

Add Review
hide form
Rating:
Name:
Email:
Subject:
Text:
  Captcha
  Add review

All ratings we receive from the items we offer are real and verified. A small gesture, but a lot of value. That's why we thank you for that minute you invest in leaving us your opinion and qualification about the products, because it helps us to continue improving and to offer you a service of even higher quality.